Keeping IEEE 1394 servo signals stable over long cable runs

The symptom
On long runs, position error appears at random: creep at low speed, occasional alarms at high speed. Swapping the drive and the motor changes nothing.
Three causes
- Shield not bonded. With the braid grounded only at the drive end, the other end floats and acts as an antenna. Bond 360° at both ends.
- Conductor too small. At 0.15 mm² over twenty metres the drop is significant and it eats the swing of a 5 V differential signal. Use 0.2 mm² or larger.
- Power and encoder cable run together. PWM couples across. Route them apart, and cross at 90° where they must.
How to confirm
Look at the differential waveform at the drive end. If eye opening falls by more than 20% over the run, check the shield first and conductor size second.